HomeAmni-Calc › Electrical › NEC Wire Sizing (310.16 & VD)

NEC WIRE SIZING (310.16 & VD)

AMPACITY TABLES, VOLTAGE DROP, CONDUIT FILL

OPEN NEC CALCULATOR →

WHAT IT COMPUTES

The NEC (NFPA 70) Table 310.16 lists allowable ampacity for insulated copper and aluminum conductors by AWG/kcmil and insulation rating (60°C, 75°C, 90°C columns). Ampacity is derated for ambient temperature (Table 310.15(B)(1)) and conductor count in conduit (Table 310.15(C)(1)). Voltage drop is recommended <3% on a single feeder or branch, <5% combined; one-way drop V_drop = 2·I·L·R / 1000 for single phase. Conduit fill is limited per Table 1 of Chapter 9 (40% for >2 conductors).

KEY EQUATIONS

References & StandardsNFPA 70 (NEC), Tables 310.16, 310.15(B)(1), Chapter 9 Table 1

WHEN TO USE THIS MODULE

Use for branch-circuit and feeder sizing in residential, commercial, and industrial installations. Determine load current first (continuous loads at 125% per NEC 210.19(A)/215.2(A)), pick conductor for ampacity at the lowest applicable termination temperature (often 75°C), then verify voltage drop. Increase conductor size if voltage drop exceeds limits even though ampacity is satisfied. Check conduit fill before specifying raceway.

RELATED MODULES

ELECTRICAL

Ohm's law, AC power triangle, three-phase, RC/RL transients

MOTORS

Synchronous speed, slip, full-load amps, torque

BATTERY

Wh / kWh, runtime, Peukert, SOC, series-parallel

PV

Hoop, longitudinal, Lamé, ASME VIII-1 minimum thickness

OPEN THE CALCULATOR

All calculations run locally in your browser. No data leaves the device.

LAUNCH NEC → ALL CALC MODULES